- This generic specification describes a prefabricated modular
Air Shower enclosure to be used for removing surface particles
from personnel prior to entering a Cleanroom work area.
- The Air Shower shall be a high velocity, low pressure
type system in accordance with Federal Standard 209E and
Air Force Tech Order 00-25-203.
- The Air Shower will provide normal entrance to and exit
from a contamination controlled area.
- The workmanship and materials shall be professional quality
and esthetically pleasing.
- The Air Shower shall be assembled and tested in the factory,
then disassembled for shipping and field assembly.
Construction
- The Air Shower shall be a completely self contained unit,
equipped with air filtration systems, blowers, motors, controls,
solid-state programmable microprocessor, interlocking doors,
lighting, and pre-wired electrical panel.
- All exterior and interior Air Shower surfaces shall be
completely sealed with materials compatible with Class 1/10
cleanroom construction standards.
- All visible surfaces shall be covered with high-pressure,
white plastic laminate. Trim shall be clear anodized aluminum.
Optional: Clad all visible surfaces with .040” clear
anodized aluminum.
- Air Shower interior air duct surface shall be completely
covered with plastic laminate, Melamine laminate, clear
anodized aluminum, or other suitable surface covering compatible
with Class 1/10 Cleanroom.
- Doors made from clear anodized aluminum and .25”
tempered glass shall be used at the entry and exit of Air
Cleanroom envelope.
- Adjustable air nozzles shall be white plastic construction
sized and spaced to provide average 7,000 fpm air flow at
the face of the nozzle.
- Return air registers shall be white baked enamel steel
grilles, built into the Air Shower wall system.
- Interior ceilings shall include an appropriate number
of air nozzles and a fluorescent light, or HEPA filters
and lighting above a protective grille (on models with laminar
flow ceilings).
- Pre-drilled and capped sprinkler penetrations shall be
provided.
Filtration System
- HEPA filters capable of removing 99.99% of dust particles
to 0.3 microns in size (optional: ULPA 99.9995% on .12 micron)
shall be used. Filter access is from above unit, or as specified.
- Air Showers which are specified to include optional Constant
Purge ceilings shall have fan-powered HEPA filters mounted
above a polystyrene egg crate diffuser panel. The Constant
Purge feature shall add 6” to the standard Air Shower
height.
- Replaceable pre-filters of 30% efficiency shall be used
to maximize life of the absolute filters and shall be accessible
from Air Shower interior, within return air grille(s).
Control System
- A Programmable Logic Controller (PLC) shall be used to
control the sequence of operation of the Air Shower.
- An Emergency Off button (EMO) shall be located inside
the Air Shower in a conspicuous location.
- Activating the switch shall cause the cycle to immediately
end, and release all interlocks. Lights shall remain on.
- Door sensors shall be 24 volt DC magnetic reed switches.
Door interlocks shall be 24 volt, located in the doorjamb
at the top of the entrance and exit ways. All locks shall
automatically release upon loss of power or when the (EMO)
button is pressed.